Critical Activities At City Gate Station (CGS)

Critical Activities At City Gate Station (CGS) 1- Pressure reduction skid CGS (active / monitor combination) with a minimum 50% redundancy including slam shut valve for over pressure protection and creep relief valves. 2- On line odorization equipment designed to minimize fugitive emissions during loading, operation and maintenance. 3- Height of the vent shall be minimum 3 meters above working level 4- Gas detectors shall be installed at critical locations 5- Pressure reduction for DRS (active / monitor combination) skid with minimum 50% redundancy including two safety devices at least one of them shall be a slam shut valve for over pressure protection and inlet /outlet isolation valves. 6- Pipeline test record and joint radiography and cover in the form of pipe book. 7- HSSE Management System. 8- Emergency Response Plan, Disaster Management Plan and written emergency procedures. Also, provide for an Emergency Control Room, manned round the clock and equipped with effective communication system and emergency vehicles fitted with communication facilities, first aid equipment, fire extinguishers, gas detectors, repair kits and tools, maps, plans, material safety data sheets etc. at its disposal.